JOB: East Jefferson Hospital
DISTRIBUTOR: Parson & Sanderson, Inc.
LOCATION: New Orleans, La
|
|
SYSTEM INFORMATION: This system is designed to supply up to 9000 gpm via four 3000 gpm Vertical Split-Case Pumps with 75 HP motors, one pump being a stand-by. System manifold connections are 20" Black Steel with 12" Multi-Purpose Valves and 12"x10" Suction Diffusers.
|
|
The system controls consist of a Johnson Metasys controller fully programmed at the Canariis factory for easy start-up and communications with the existing Energy Management System at the Hospital. Canariis will match any Energy Management System for easier integration of the Packaged Pumping System with the rest of the facility which saves time, money and personnel training.
|
|
The Condenser Water Package has been designed for outdoor operation with the system being mounted on the roof with the cooling towers.
|