JOB: J.T. Mather Hospital
DISTRIBUTOR: Hugh J. Cullen Associates
ENGINEER: Cannon
CONTRACTOR: Botto Mechanical Construction
SYSTEM INFORMATION: Triplex Space Saver Domestic Water Booster System designed for a system capacity of 480 GPM at a system pressure of 47 PSIG. This booster pump package is designed for intermittent run with the lag pumps starting through pressure switch sequencing when the demand requires. The system options include a Control Power Switch and Light, Low Suction Pressure Shutdown, Low Pressure Circuit to Start Standby Pumps, High System Pressure Shutdown Circuit, Audible Alarm with Silence Push Button, Auto Alternate 3 Equal Pumps, Individual Pump Temperature Probe and Purge Valves for Thermal Protection and Auxiliary Relay Contacts.
|
|