System Design Index | Definitions | Pump Differential Pressure Required | System Capacity(GPM) | Number, Size, Horsepower and Type of Pumps | System Valves, Manifold Size and Hydro-Pneumatic Tanks | System Controls | Sequencing of Pumps | Control Panel Features and Options
System Capacity (GPM)
  1. The designer must take into consideration the type of building and the activities of the occupants. These factors - particularly the human element - cannot be covered by engineering formula, so it becomes necessary to rely on operating data and records compiled over the years by various users, manufacturers and trade associations. We recommend using the data as detailed below as follows.

  2. Assign the indicated number of fixture units to each individual fixture in the piping system that the booster will serve using the fixture unit table below.

  3. Total the fixture units for the entire system.

  4. Convert the total fixture units to a fixture peak demand in GPM using the fixture peak demand curves.

  5. Add the flow required for any special duty. The capacity charts show fixture peak demand only. Special requirements such as air conditioning apparatus, process equipment, boiler makeup, swimming pools, etc., must be estimated separately and added to the fixture demand.

    NOTES:

    1. Occupancy - Capacity ratings are based on the assumption that an equal number of men and women are to be accommodated. Where the occupancy is predominantly female, increase the total pumping capacity by 15%.

    2. Laundries - In the case of hotels and hospitals, where a laundry is operated in connection with the building, increase the total pumping capacity by 10%.

    1. FIXTURE PEAK DEMAND   _______GPM
    2. SPECIAL DUTY DEMAND   _______GPM
    3. SYSTEM CAPACITY(1 + 2) _______GPM

    Fixture
    Type of Supply
    Control
    Fixture Units
    Number of
    Fixtures
      Total  
    Bathroom Group
    Flush Valve
    8
     
     
    Bathroom Group
    Flush Tank
    6
     
     
    Water closet
    Flush Valve
    10
     
     
    Water closet
    Flush Tank
    5
     
     
    Urinal
    Flush Valve
    5
     
     
    Sink - Kitchen
    Faucet
    2
     
     
    Sink - Service
    Faucet
    4
     
     
    Dishwasher
    Automatic
    2
     
     
    Washing machine
    Automatic
    4
     
     
    Hose connection, 1/2"
    Faucet
    4
     
     
    Total Fixture Units
     